Zhuhai Kehui Electric Appliance Co., Ltd
Home>Products>YTJQ10-XX 10kV airtight three-phase AC voltage sensor
Product Groups
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
    13825655906
  • Address
    No. 8 Jinrui 1st Road, Jinding National High tech Zone, Zhuhai City, Guangdong Province
Contact Now
YTJQ10-XX 10kV airtight three-phase AC voltage sensor
YTJQ10-XX 10kV airtight three-phase AC voltage sensor
Product details


1、 Overview

YTJQ10-XX 10kV airtight three-phase AC voltage sensor, based on the principle of capacitive voltage division, is small in size, light in weight, and simple in structure. Applicable toZW20type/ZW28Column mounted switchSF6Measure the three-phase voltage and zero sequence voltage of power lines in the gas chamber to meet the requirements of primary and secondary integration of distribution network automation.

Product Model:YTJQ10-XXseries

Product naming convention:



1、 Product Features

Adopting the principle of capacitive voltage division, it has high accuracy, good linearity, and wide frequency band

● Small size, light weight, low power consumption, suitable for placement inZW20/ZW28SwitchedSF6In the air chamber

There is no ferromagnetic saturation or ferromagnetic resonance

● Primary and secondary isolation, safe and reliable

Low output voltage, no risk of secondary short circuit and high current

● Wide temperature range(-40℃~70℃)

● High insulation impedance (>)1000MΩ)

There is no interface layering issue, safe and reliable

● Strong load capacity(1MΩ), the cable length can reach15rice

Three in one cable output signal, easy to connect

2、 Execution and reference standards:

1. T/CES 018-2018 Distribution Network10kVand20kVExchange sensor technology specifications

2. GB/T 20840.7-2007 Transformers7Part: Electronic Voltage Transformer

3. DL/T 1155-2012 Technical conditions for non-traditional transformers

4、 Basic parameters

4.1. Rated primary voltage:10kV/3

4.2. Rated secondary voltage:3.25V/3

4.3. Rated secondary zero sequence voltage(three-phase)6.5V

4.4. Accuracy level:0.23P)The13P

4.5. Rated voltage factor:1.2(continuous)1.98h

4.6. Rated load:1MΩ

4.7. Partial discharge level: ≤10pC(14.4kV)

4.8. Power frequency withstand voltage:48kV/1min

4.9. Lightning impulse withstand voltage:75kV/85kV

4.10. Working environment:-40℃~70(Allow temperature rise45K)

4.11. Service life: ≥15year

5、 Structural parameters:

5.1. Structural dimensions are shown in the diagram1



5.2. Wiring diagram as shown in the figure2