Application and Characteristics
1. Fully comply with the GB/T50378-2014 "Green Building Evaluation Standard";
2. By using high-precision MEMS sensors and digital technology, CO2 concentration values can be verified;
3. Merge power communication into two cables and two bus communication;
4. Provide feedback on indoor CO2 concentration values and sensor malfunction information;
5. DC24V safe working voltage, independent address coding;
6. Dimensions: 130 * 110 * 42mm;
7. Online continuous monitoring and real-time display of monitoring values.
technical indicators
Sensor: NDIR sensor with ABC self calibration function
Measurement principle: active gas diffusion
Response time:<10s (30cc/min, slow flow air)
Drift:<± 10ppm/year
Range: 0-200ppm, or other (0-5000pm)
Output: 4-20mA, 0~10V, RS485/Modbus
Relay: 2 x SPST,
CDW/CDD∶1A/30VDC, 0.5A/125VAC
CDWN∶3A/30VDC,3A/250VAC
Output load: ≤ 500 Ω (current type), ≥ 2K Ω (voltage type)
Power supply: 15~28VAC/15~36VDC
Working environment: 0-50 ℃, 0-95% RH (non condensing)
Storage and transportation temperature: -20~80 ℃
Shell material: Fireproof ABS
Protection level: IP30 (CDWCDWN), IP65 (CDD)