>product overview
WIDEPLUS-CTThe pressure transmission controller is a multifunctional product that integrates pressure measurement, display, control, and microcomputer communication. This product is a fully electronic structure, with a pressure sensor with an oil filled core with an isolation film at the front end. The output signal is sent to the microprocessor by a high-precision, low-temperature drift, and high reliability amplification circuit and analog-to-digital conversion circuit. After calculation, the high-precision analog-to-digital conversion circuit converts the data into a standard signal output. Equipped with five independent relay contact outputs, it can directly replace the electric contact pressure gauge. It is flexible to use, easy to operate, and easy to adjust. It is widely used in various industries such as power, tap water, water treatment, petroleum, chemical, and metallurgy to measure, display, control, and remotely transmit the pressure of fluid media. It is an intelligent digital pressure measuring instrument.
>Technical Parameter
analog output(4~20)mA DC (Load resistance ≤750Ω)
0~10 mA DC (Load resistance ≤1.5KΩ)
(1~5)V DC (Load resistance ≥250K)
0~5V DC (Load resistance ≥250K )
Switching Output Relay control output—ON/OFF(Bring back the difference)
CONTACT CAPACITYAC220V/2A;DC 24V/2A(Resistive load)
Controllable silicon control output— SCR (Zero crossing trigger pulse)output:AC 400V/0.5A
Solid state relay output—SSR(Solid state relay control signal)output:(5~24)V DC/30mA
Communication output Standard serial bidirectional communication interface
Communication protocol:RS-232C,RS-485
Baud rate: (300~9600)bps(Free setting)
measuring range Relative pressure maximum0~60MPaminimum0~20kPa
absolute pressure maximum0~60MPaminimum0~20kPa
Negative relative pressure(-0.1~1)MPa
measurement accuracy ±0.2%FSperhaps±0.5%FS
dividedistinguishrate ±1character
Display Range -1999~9999
Display mode Four digit high brightnessLEDDigital display, LED working status display, dual screen digital display
control/call the police Can choose upper limit, lower limit or upper limit, lower limit control/ALARM IN
Method relayON/OFFBring back the difference (can be freely set)
Parameter setting Panel touch sensitive button numerical setting, parameter setting value permanently saved after power failure, parameter setting value password locked
Protection method Relay output statusLEDindicate,Input over/under range alarm,Automatic reset of power supply under voltage or abnormal operation
Environmental temperature -10℃~60℃
Relative humidity ≤85% RH(Avoid strong corrosive gases)
Supply voltage·(90~265) V AC (Switching power supply) ·DC24V±2V(Switching power supply)
Power consumption ·≤4W (90~265) V AC (Switching power supply) ·≤4W(DC24V(Switching power supply)
Structural materials Pressure interface: stainless steel
Pressure sensitive film:316Lstainless steel
Electronic casing: aluminum alloy or iron casing
Sealing rubber ring: Fluorine rubber, nitrile rubber or fully sealed welded
>External dimensions(unit:mm)

>WIDEPLUS-CTSeries pressure transmission controller type spectrogram