VIP member
TXK-F self-contained power plant dedicated arc and harmonic suppression device
TXK series complete equipment selection guide note: P: distribution type Capable of determining the grounding function of arc light inside and outside
Product details
TXK series complete equipment selection guide
Note:P: Distribution type It has the function of determining the arc grounding inside and outside the station.
B: Substation type Suitable for use in substation systems.
M: Coal mine specific type Capable of activating the arc suppression coil
F: Special type for self owned power plants Introduce the zero sequence lockable arc suppression function of the generator.
Scope of Application
TXK-F is suitable for small current grounding systems with high voltage generators or high voltage motors of various voltage levels from 6KV to 35KV.
Working principle
Non generator stator arc grounding
When the non generator stator is grounded by arc light, the intelligent controller quickly issues a command to close the corresponding phase contactor;
If the intelligent controller is set to automatic recovery state, the device will automatically recover according to the user's set time and open the grounding contactor;
The device records various parameters at the time of the fault;
The device simultaneously emits an alarm signal.
Generator stator experiences arc light or metal grounding
When the device detects arc light or metal grounding in the generator stator, the intelligent controller reliably locks the arc extinguishing device and only alarms.
Metal grounding
When metal grounding occurs in the non generator stator system, the intelligent controller selects the grounding contactor or alarm according to user requirements;
If the intelligent controller is set to an automatic recovery state, the device will automatically recover according to the user's set time and open the grounding contactor;
The device simultaneously emits an alarm signal.
PT disconnection
When the system experiences PT disconnection, the intelligent controller sends an alarm signal.
Main functions
The device can quickly and reliably operate when the system experiences arc grounding, converting the arc grounding phase into high-frequency damping grounding;
The device can introduce up to 6 generators or high-voltage motors with zero sequence current; When the stator arc of the generator (motor) is grounded, the device can accurately determine and lock the arc extinguishing action function
After arc grounding, the recovery method of the device can be flexibly set: manual recovery, delayed automatic recovery, and automatic conversion to manual recovery after two actions can be achieved. The delay time and recovery method can be set according to on-site requirements;
● System overvoltage protection function;
Intelligent harmonic elimination function can eliminate various resonances from 0-300Hz, and the harmonic elimination component adopts the constant current principle
Intelligent line selection function (optional)
When the system malfunctions, the device can record the data at the moment of the malfunction, which is convenient for maintenance personnel to refer to and analyze the cause of the accident;
After the arc grounding action, the device can record and store the instantaneous capacitance current value of the grounding system for system analysis;
The device has the functions of background time synchronization and parameter modification, which can achieve remote control and signal reset, and is practical for unmanned substations;
The device provides RS485 communication mode, standard MODBUS RTU protocol, and easy networking.
trtd001@163.com