ACVATIX ™ Siemens electric valve actuator SAX61.03 SAX31.00 SAX81.00
·SAX31.00 working voltage AC 230 V, three digit control signal
·SAX61.03 working voltage AC/DC 24 V, control signal DC 0... 10 V, 4... 20 mA
·SAX81.00 working voltage AC/DC 24 V, three digit control signal
·SAX61.03 valve position feedback, priority control, optional flow characteristics
·Can be directly installed on the valve; No adjustment needed
·Equipped with manual adjuster, position indicator and LED status display
·Optional auxiliary switches, potentiometers, functional modules, valve stem heating elements, etc
purpose
The Siemens electric actuator SAX series (SAX61.03 SAX31.00 SAX81.00) is used for HVAC system control and safety shut-off. It includes Siemens V.F31., V.F40., V.F42., V.G41., V.I41., and VVF53. series models of two-way and three-way regulating valves, or our company's two-way and three-way electric regulating valves and temperature control valves, with a driving stroke of 20mm.
Model Overview
| Product Model | itinerary | reasoning | power supply | control signal |
positioning time |
manual adjust |
enhance function |
| SAX31.00 | 20mm | 800N | AC230V | 3 people | 120S | Push and fix | |
| SAX31.03 | 30S | ||||||
| SAX61.03 SAX61.03U |
AC24V | DC 0…10 V DC 4…20 mA 0 to 1000Ω |
Valve position feedback Compulsory control Change control characteristics |
||||
| SAX81.00 SAX81.00U |
3 people | 120S | |||||
| SAX81.03 SAX81.03U |
30S |
Electronic accessories

Mechanical Parts

The Siemens electric actuator SAX series (SAX61.03 SAX31.00 SAX81.00) is supplied in independent packaging with valves and accessories.
Attention
engineering application
Three actuators must use dedicated controllers.A controller with a rated output value of 1 mA can drive up to 10 actuators in parallel.
The input impedance of the analog actuator is 100 k Ω.
install
maintenance
The actuator does not require maintenance.
guarantee
When the Siemens electric actuator SAX series (SAX61.03 SAX31.00 SAX81.00) is connected and used with valves from other manufacturers, the user must ensure that its function is normal, and Siemens does not assume any responsibility.
Technical data
power supply
|
Working voltage:
SAX31.. AC 230 V ±15% SAX61.. AC 24 V ± 20% / DC 24 V + 20% / -15% SAX81.. AC 24 V ±20% / DC 24 V + 20 % / -15% Frequency: 45... 65Hz Fuse fuse for power cord: maximum 10A slow melting Power consumption at 50 Hz: SAX31.00 stem contraction/elongation 3.5 VA/2 W SAX31.03 Valve stem contraction/elongation 8 VA/3.5 W SAX61.03. Valve stem contraction/elongation 8 VA/3.75 W SAX81.00. Valve stem contraction/elongation 3.5 VA/2.25 W SAX81.03. Valve stem contraction/elongation 8 VA/3.75 W |
functional data
|
Positioning operation time (specifically referring to rated stroke), the positioning operation time varies depending on the valve model
SAX31.00, SAX81.00.. :120 s SAX31.03, SAX61.03.., SAX81.03.. 吗: 30 s Rated thrust: 800 N Rated travel: 20 mm Allowable medium temperature (with valve): -25... 150 ° C |
signal input
|
Control signal "Y" SAX31., SAX81. 3-bit SAX31.: Voltage AC 230 V ± 15% SAX81.: Voltage AC 24V ± 20%/DC 24V+20%/-15% SAX61.: (DC 0... 10 V) Current consumption ≤ 0.1 mA Input impedance ≥ 100 k SAX61.: (DC 4... 20 mA) Current consumption DC 4... 20 mA ± 1% Input impedance ≤ 500 Parallel operation: SAX61. ≤ 10 (depending on the output of the controller) |
Valve position feedback
|
SAX61.. Valve position feedback: U DC 0... 10 V ± 1% Load impedance:>10 k res Maximum load: 1 mA SAX31.. SAX81.. Auxiliary switch required: ASC10.51 |
compulsory control
|
SAX61.. Control signal: "Z" R=0... 1000, G, G0 R=0... 1000 trips are proportional to R Z connects to G with a maximum travel of 100% Z connects to G0 with a minimum travel of 0% 1) Voltage: Maximum AC 24 V ± 20% Maximum DC 24 V+20%/-15% Current consumption: ≤ 0.1 mA |
standard
|
Meet CE standards Compliant with the EMC Electromagnetic Compatibility Directive 2004/108/EC Anti interference EN 61000-6-2: [2005] Industrial Radiation EN 61000-6-3: [2007] Residential Electrical safety EN 60730-1 Low Voltage Directive AC 230 V 2006/95/EC C-tick N 474 UL certified AC 230 V - AC/DC 24 V UL 873 |
Protection level
|
Vertical to horizontal enclosure IP54 according to EN 60529 3) Insulation level according to EN 60730 Executive SAX31. AC 230 V II Actuator SAX61. AC/DC 24 V III Actuator SAX81. AC/DC 24 V III |
Environmental Reliability
|
ISO 14001 (Environment) ISO 9001 (Quality) SN 36350 (Environmental Reliability Product) RL 2002/95/EG (RoHS) |
environmental conditions
|
Operation: IEC 60721-3-3 Climate conditions: 3K5 level Installation location: Indoor (weatherproof) Basic temperature range: -5... 55 ° C Heating element with valve stem ASZ6.6: -15... 55 ° C Humidity (non condensing): 5... 95% r.h Transportation: IEC 60721-3-2 Climate conditions: 2K3 level Temperature: -25... 70 ° C Humidity:<95% r.h Storage: IEC 60721-3-1 Temperature: -15... 55 ° C Humidity: 5... 95% r.h Maximum medium temperature when installed on the valve: 150 ° C |
accessories
|
Potentiometer ASZ7.5/135:0... 135 ± 5% Voltage: DC 10 V Rated current:<4 mA Potentiometer ASZ7.5/200:0... 200 ± 5% Voltage: DC 10 V Rated current:<4 mA Potentiometer ASZ7.5/1000:0... 1000 ± 5% Voltage: DC 10 V Rated current:<4 mA Auxiliary switch ASC10.51: Switching capacity AC 24... 230 V, 6 A res., 3 A ind Valve stem heating element ASZ6.6: AC 24 V, 30 W |
size