Overview
Name |
ID |
Product Description |
Δpmax |
Δps |
kvsRated flow coefficient when the valve is fully open |
nominal diameter |
|---|---|---|---|---|---|---|
M3P100FY |
100325486 |
Continuous regulating three-way mixed flow/two-way electromagnetic regulating valve, flange connection, PN16, DN100, kvs 130, AC 24 V |
200 kPa |
200 kPa |
130 m3/h |
100 |
M3P80FY |
100325489 |
Continuous regulating three-way mixed flow/two-way electromagnetic regulating valve, flange connection, PN16, DN80, kvs 80, AC 24 V |
300 kPa |
300 kPa |
80 m3/h |
80 |

function
BPZ:M3P. .FY..
Analog regulating valve for chilled water or low-pressure hot water, PN16
A hybrid three-way or two-way valve with electromagnetic actuator, suitable for analog control of chilled water or low-pressure hot water in closed-loop systems. Flange connection, with positioning control, valve position feedback signal, spring reset and manual function.

technical specifications
rated pressure |
PN 16 |
Working Voltage |
AC 24 V |
Positioning signal |
DC 0...10 V; DC 4...20 mA |
positioning time |
Close:<2 seconds |
Equipped with spring reset function |
1->3 Close |
position feedback |
DC 0...10 V |
Protection level |
IP31 |
ambient temperature |
2...50 °C |
Installation location |
Vertical to horizontal |
Allow work pressure |
1000 kPa |
leakage rate |
Leakage rate 1->3 not exceeding 0.05% kvs |
Bypass leakage rate |
ca. 2 % of kvsvalue |
medium temperature |
1…120 °C |
Valve flow characteristics |
linear |
Travel accuracy Δ H/H100 |
1:1000 |
valve body |
Cast iron GG20 |
Valve internal material |
Chromium nickel steel/brass |
Technical Specifications Table |
N4454 |