Technical Parameter
|
Technical Parameter |
index |
|
|
accuracy class |
Voltage: 0.2 level; Current: 0.2 level; Frequency: 0.05Hz; Power factor: Class 0.5 |
|
|
Active power: Level 0.5; Reactive power: Level 0.5; Visual power: 0.5 level |
||
|
Active energy: 0.5S level/1 level; Reactive power: Level 2 |
||
|
INPUT |
RATING |
Rated voltage: 100V/400V; Current: 1A/5A |
|
overload |
Current: continuous 1.2 times, instantaneous 10 times/S; Voltage: continuous 1.2 times, instantaneous 2 times/S |
|
|
frequency |
Frequency 45-60 (Hz) |
|
|
functional module |
Electric pulse output |
2-channel power pulse output |
|
communication interface |
2-channel RS485, Modbus RTU, baud rate: 1200-19200 (bps) |
|
|
Working power supply |
scope of work |
AC:85~265V; DC:85~300V |
|
power consumption |
< 3W |
|
|
work environment |
temperature |
Work: -20 ℃~+70 ℃; Storage: -40 ℃~+80 ℃ |
|
humidity |
Relative humidity ≤ 93%, non corrosive gas environment |
|
|
altitude |
≤4000m |
|
|
Installation method |
Standard guide rail installation, external dimensions: 210 × 100 × 45 (mm) |
|