MI3123Grounding resistance tester
Main features of MI3123 grounding resistance tester:
All methods including grounding resistance testing: standard four wire method, selected electrode method, double clamp method, soil resistivity measurement
Clamp type current measurement function, range 0-20A, resolution 0.1mA
Strong anti-interference ability
Pre programmed limit, pass/fail (PASS/FAIL) evaluation of measurement results
Green/red indicators provide intuitive evaluation of measurement results
Suitable for CAT IV device acceptance
The built-in magnet can fix the instrument on iron materials
Built in charger
Can store 1900 measurement results
USB/RS232 communication interface, compatible with PCSW software
Sturdy and exquisite instrument appearance design
Compliant with standards: IEC/EN 61557-1, 5, 10, IEC/EN 61010-1, IEC/EN 61326,
Technical specifications of MI3123 grounding resistance tester:
Four line method/selective electrode method measurement
Automatic testing of grounding resistance for grounding piles and interference in voltage signals
Test voltage (open circuit) 40V Test frequency 125Hz
Maximum test current 20mA, current clamp test current too low indication
Excessive interference indication in current signal
MI3123 Grounding Resistance Tester Double Clamp Method for Measuring Grounding Resistance
| Measurement range (W) |
Resolution (W) |
precision |
| 0.00-19.99 |
0.01 |
3% reading+3 digits |
| 20.0-199.9 |
0.1 |
3% reading+3 digits |
| 200-1999 |
1 |
5% reading |
| 2000-9999 |
1 |
10% reading |
Test frequency 125Hz, interference indication, low current indication
MI3123 Advanced Universal Grounding Resistance Tester for Soil Resistance Measurement
| Measurement range (Wm) |
Resolution (Wm) |
precision |
| 0.0-99.9 |
0.1 |
Soil resistivity is a calculated value, and the accuracy refers to the precision of measuring grounding resistance using the four line method |
| 100-999 |
1 |
| 1.00k-99.9k |
0.01k |
| 10.0k-99.9k |
0.1k |
| >100k |
1k |
Isometric method, r=2pDR
MI3123 Grounding Resistance Tester Current Measurement
| measurement range |
Resolution (mA) |
precision |
| 0.0-99.9mA |
0.1mA |
3% reading+3 digits |
| 100-999mA |
1mA |
3% reading+3 digits |
| 1.00A-19.99A |
0.01A |
3% reading+3 digits |
Frequency range: 40-500Hz
Basic technical parameters of MI3123 grounding resistance tester
power supplyNumber 5 1.5V rechargeable battery, 6 cells, approximately 10 hours of operation time
Overvoltage protection: 50V CAT IV
Display: 128X64 backlit LCD screen
Size: 14cmX8cmX23cm
Weight: 0.85kg
MI3123 Grounding Resistance Tester Ordering Information:
Standard configuration:Host, 1 set of 20 meter test line and grounding post, rechargeable battery and charger, A1018 current clamp
A1019 current clamp, user manual
MI3123 Grounding Resistance Tester OptionsA1290 software
S2007 50 meter test line