project/certification
• FM
• UL
• VdS
• CFE
• CE - EMCTheLVDandCPD
• EN54-20
feature
* single zone
* Dual tube air sampling
* 0.001%-20%shading rate/Rice(0.0003%-6.10%
* shading rate/Feet)
* 4Level alarm-Warning, action, fire alarm1、 火警2
* 2x100Rice(2x328Foot sampling tube
* Performance enhanced suction pump
* EthernetTCP/IPagreement
* RS232andRS485 Modbusbus
* Optional additional relay output
* optional4to20Milliampere analog output
* The maximum coverage area can reach:
* ForVdSInstallation, for2000Square meters(21500Square feet)
* ForULInstallation, for850Square meters(9150Square feet)
Specifications
|
power supply voltage |
nominal24Volt DC |
|
power supply current |
500Milliampere (minimum) to1.2Ampere (maximum) |
|
getter device |
2000Pa centrifugal air pump |
|
Size (width, height, height) |
254millimeterx180millimeterx165millimeter (10.0inchx7.1inchx6.5Inches) |
|
working conditions |
Temperature:-10to60°C(14to140°F) Humidity: Relative humidity 10to95%(Non condensing) |
|
Sampling tube size |
Outer diameter:25millimeter |
|
Sampling pipeline network |
Region:1A fire prevention zone Manager:2x100Rice(2x328Feet) |
|
Alarm sensitivity range |
0.001%-20%shading rate/rice (0.0003%-6.10%shading rate/Feet) |
|
Alarm Settings |
Alarm level: Warning Action, fire alarm1、 火警2 Alarm delay:1-60second Can independently program alarms at all levels |
|
IPProtection level |
IP65 |
|
filter |
Cleanable, maintainable, and reusable dual components filter |
|
Airflow monitoring |
Dual thermal sensing element |
|
relay output |
4The alarm relay of the department,1The faulty relay,1Department release Large converter rated 1An@30Voltage DC, normally open/normally closed contact |
|
communication |
RS232TheRS485 Modbus EthernetTCP/IP |
|
Event log |
up to20000Event storage records |