Product Introduction
|
Single channel, dual channel (isolated). |
summary
| Certificate No | GYB081021 |
| Explosion proof sign | [Exia] IIC (National Explosion proof Safety Supervision and Inspection Station Certification for Instruments and Meters) |
| Authentication parameters | |
| terminal | 8-7, 11-10 |
| Maximum allowable voltage | Um=250V |
| voltage | Uo=10.5V |
| electric current | Io=16mA |
| power | Po=42mW |
| capacitance | Co=2.4μF |
| inductance | Lo=80mH |
Single input single output wiring diagram
Dual input dual output wiring diagram
| terminal number | Terminal Description | |
| Safe Zone (Green) | 1 | OUT1A(S-) |
| 2 | OUT1B(S+) | |
| 3 | OUT2A(S-) | |
| 4 | OUT2B(S+) | |
| 5 | POW(+) | |
| 6 | POW(-) | |
| Dangerous Zone (Blue) | 7 | IN1A |
| 8 | IN1B | |
| 10 | IN2A | |
| 11 | IN2B | |
Application 1: Transistor collector output Application 2: Transistor emitter output
Structural Outline Drawing
| EVT1/EVT2: Working indicator light: When the input signal is short circuited, the indicator light is green; When the input signal is disconnected, the indicator light is red. |
| 35mm guide rail installation, please pay attention to stable and firm positioning during installation. |
| Please install it vertically as much as possible to facilitate heat dissipation inside the instrument. |
| power supply | |
| Rated working voltage range | DC 24V±10% |
| power consumption |
Single output: ≤ 0.8W, dual output ≤ 1.2W |
| Dangerous side | |
| Input Signal Type | Contact switch, proximity switch (frequency ≤ 5KHZ) |
| Distribution voltage | ≈ 8V (open circuit) |
| Short circuit radio wave | ≈8mA |
| Safety side | |
| Output signal type | Relay/transistor |
| Relay output driving capability | 125VAC/0.6A 30VDC/2A |
| Relay response time | <5ms |
| Transistor output | When collector output (see application 1 for wiring method): High level VCC (≤ 30V), low level ≤ 2.5V |
| When the emitter outputs (see application 2 for wiring method): high level VCC-2.5V, low level ≤ 0.5V | |
| Input and output characteristics (when set to in-phase control) | |
| On site switch closed or input circuit current>2.1mA, output relay or transistor conducting, channel green indicator light on | |
| On site switch open circuit or input circuit current < 1.2mA, output relay or transistor non-conductive, channel red indicator light on | |
| Input and output inverse control settings | |
| Set by panel dial switch J5 (see accompanying manual for details) | |
| Dielectric Strength | |
| Local security end and non local security end | 2500V,a.c; 1min |
| environmental condition | |
| ambient temperature | 0~50℃ |
| ambient humidity | 5% to 95% RH (non condensing) |
| Standard | |
| electromagnetic compatibility | Compliant with GB/T18268 Industrial Equipment Application Requirements |
instrument selection
| 7 | 8 | 9 | 10 | ||||||||
| Switch input detection terminal isolation gate NHR-A35 | - | □ | / | □ | - | □ | / | □ | |||
| position | specifications | explanatory note |
| |
|
| | | ↓ □ |
| | | | | | | | | | ↓ □ |
|
| | | | | | | | | | ↓ □ |
|||
| 7/8 | <Input> | ||||||||||
| Input I/Input II (select code from list) | |||||||||||
| code | Type | ||||||||||
| X | No input (limited to output II) | ||||||||||
| 36 | Switching quantity | ||||||||||
| 9/10 | <Output> | ||||||||||
| Output I/Output II (select code from list) | |||||||||||
| code | type | ||||||||||
| X | No output (limited to output II) | ||||||||||
| K1 | Relay contact | ||||||||||
| K2 | transistor | ||||||||||
Switch input detection terminal isolation gate, dual input signal is switch quantity, dual output is relay contact signal.