VIP member
Fulai 28500SM Central Air Conditioning Fully Automatic Softening Water Treatment Equipment Boiler Fully Automatic Softener Spot Sales
Fulai 28500SM central air conditioning automatic softening water treatment equipment boiler automatic water softener adopts the FLECK automatic contro
Product details
The Fulai 2850 valve is suitable for single valve and single tank systems. If used for dual tank systems, an additional valve is required to achieve this.
| 2850Technical characteristics of control valve | |||
| Valve body material | Lead free brass | ||
| enter/出口管径 | 1-1/2” | ||
| Flow range(0.35MPaInlet pressure | |||
| Continuous water output (pressure drop)0.1MPa) | 11.5m3/h | ||
| Peak water output (pressure drop)0.175MPa) | 15m3/h | ||
| drag coefficientCv | 13.2 | ||
| Backwash flow rate (pressure drop)0.175MPa) | 49gpm | ||
| Regeneration: downstream flow/against the current | downstream | ||
| Program adjustment | The regeneration step time can be adjusted | ||
| *Large regeneration time | 164minute | ||
| Flow meter accuracy1” | 0.159~9.09m3/h±5% | Power parameters | 220V-50Hz |
| 1-1/2” | 0.34~17.04 m3/h±5% | design pressure | 2.1MPa |
| Flow meter range1” | standard1.17~19.96 m3 | work pressure | 0.14~0.84MPa |
| increase5.87~99.81 m3 | Operating Temperature | 5℃~55℃ | |
| 1-1/2” | standard2.36~40.24 m3 | ||
| increase11.83~201.23 m3 | |||
| No hard water bypass | yes | ||
| Main dimensions: | work procedure | Time setting reference | |
| Central tube diameter | 1.5”I.D. | 1.backwashing | 10minute |
| Diameter of drainage pipe | 1”(Male) | 2.Salt absorption displacement | 60minute |
| Diameter of salt solution pipe | 1/2”, ( 3/8”) | 3.Washing in progress | 10minute |
| Diameter of tank interface | 4”-8UN | 4.Salt box water replenishment | 10minute |
| Valve body height (from the top of the valve body to the tank interface) | 6-1/2”The165mm | 5.run | |
| Tank dimensions | soften | |||||
| diameter | Backwash flow rateDLFC | Regeneration System | injector | Salt safety valve, air check valve | B.L.F.C. | |
| in | mm | gpm(5gpm/ft2) | gpm | |||
| 10 | 254 | 2.4 | 1600(1610) | 1 | 2310OR2300,500Air Check | 0.5 |
| 12 | 305 | 4.0 | 1600(1610) | 2 | 2310OR2300,500Air Check | 0.5 |
| 13 | 330 | 4.6 | 1600(1610) | 3 | 2310OR2300,500Air Check | 1 |
| 14 | 356 | 5.0 | 1600(1610) | 4 | 2310OR2300,500Air Check | 1 |
| 16 | 406 | 7.0 | 1600(1610) | 4** | 2310OR2300,500Air Check | 1 |
| 18 | 457 | 8.0 | 1700 | 4C | 2350,900 Air Check | 2.4 |
| 21 | 533 | 12.0 | 1700 | 4C | 2350,900 Air Check | 2.4 |
| 24 | 610 | 15.0 | 1700 | 5C | 2350,900 Air Check | 3 |
| 30 | 762 | 25.0 | 1700 | 6C | 2350,900 Air Check | 5 |