DTS (X) 6111 three-phase four wire active and reactive combination meter (LCD)
DTS (X) 6111 three-phase four wire active and reactive combination meter (LCD)
Product details


6. Main functions

6.1 Measurement Function

6.1.1 Measure active and reactive electrical energy and store their data.

6.1.2 Electric energy is calculated, displayed, and stored separately based on the positive and negative active power and total reactive power.

6.1.3 Positive and negative active and non functional electricity, repeated power-off and power on operations do not affect the accuracy of the energy meter;

6.1.4 Indicator lights

When there is a power pulse signal, light up the pulse indicator light (one for active and one for reactive power) for about 80 ± 20ms.


1. Overview

DTS (X) 6111 and DSS (X) 6111 three-phase electronic active and reactive combined energy meters (hereinafter referred to as energy meters) are developed to adapt to the design and renovation of power grids. It has high accuracy and feasibility. The product manufacturing standards comply with all technical requirements for three-phase static energy meters in the power industry standards such as GB/T17215.321-2008 "Level 1 and Level 2 Static AC Active Energy Meters", GB/T17215.323-2008, DL/T614-1997 "Multi functional Energy Meters", DL/T645-1997 "Multi functional Energy Meter Communication Protocol", etc. It is an ideal choice for enterprises, substations or power plants that require reactive power assessment, and is also suitable for use in transmission and distribution or distribution automation. This product can measure three-phase AC active and reactive energy in a 50Hz reference frequency power grid, and can perform forward and reverse energy measurement as well as infrared and RS485 communication functions. Its characteristics are high precision, good reliability, wide load, low power consumption, straight error curve, and strong anti-interference ability.

2. Working principle

2. Working principle of electric energy metering unit


Working principle of electric energy metering unit

The current of each phase of the measured electrical energy is sampled by a transformer to obtain a voltage signal, which is then amplified by the differential amplifier circuit inside the ATT7026A chip. The amplified signal is converted into a digital signal proportional to it through A/D conversion, and after high pass filtering to remove the DC component in the signal, it enters one input terminal of the digital multiplier. The voltage signal of the measured electrical energy is sampled through resistance voltage division, and then passed through

The differential amplifier circuit inside the ATT7026A chip amplifies the signal, and then converts it into a digital signal proportional to it through A/D conversion. It enters the other input of the digital multiplier and multiplies the signal from the current channel

Calculate and complete the instantaneous power measurement of the measured electrical energy. The instantaneous power output of each phase is integrated through a digital low-pass filter, and then the absolute value is accumulated before entering the 'digital/frequency' converter. The pulses output by the frequency divider circuit are isolated and sent to the CPU unit for processing, recording the total active and reactive power and the active reverse power respectively.

3.2 Working principle of CPU unit

The high-frequency pulses output by the energy metering unit are passed through two optocouplers, one of which is used as a passive pulse output for factory inspection and user verification of the energy meter; Another route is sent to the CPU chip for data processing. Under the instructions of the system (energy meter program), the CPU calculates the active and reactive power values based on the memory and instrument constants in the data storage, and then transfers them to the internal memory. The stored data can be displayed on the LCD,

It can also be output through two communication methods: infrared and RS485.

3. Technical indicators

·Reference frequency: 50Hz;

·Reference voltage: three-phase four wire

3X220/380V, 3X57.7/100V;Three phase three wire 3X380V, 3X100V;·Current specification: Connected through transformer type:3X1.5(6)A、 3X(6)A;Direct access type:

3X5(20)A

、 3X10 (40) A, 3X15 (60) A, 3X20 (80) A, 3X30 (100) A;


1

·Instrument constant: 100imp/kWh-6400imp/kWh (as indicated on the nameplate);

·Accuracy level: active power level 1, reactive power level 2;

·Starting: Under the conditions of reference voltage, reference frequency, and power factor of 1.0, the active power of 0.004 Ι b (level 1) and the reactive power of 0.005 Ι n (level 2) of the energy meter can start and continuously measure electrical energy.


·Stealth: It has a logic anti creep function. When the voltage circuit is added with a reference voltage of 115% and the current circuit is disconnected, the energy meter does not generate an additional pulse output.

-25·Climate conditionsThe specified working temperature range55

-40Extreme operating temperature range70

-40Extreme temperature range for storage and transportation70


relative humidity

Annual average ≤ 75%

·Electrical parameters

Normal operating voltage range

0.8-1.1 reference voltage

Extreme working voltage range

0.7-1.2 reference voltageVoltage circuit power consumption

6VA/2W

Current circuit power consumption

≤2VA10Data retention time after power outage

year

4. Size and weight

4.1 Outline and Installation Dimensional Diagram

3

4.2 Dimensions: 270X170X79mm; Installation size: 240X150mm





4.3 Weight:

About 2kg

5. Installation and use

·Experienced electricians or professionals are required to install an energy meter and ensure that they have read this manual thoroughly;

·Take out the energy meter from the packaging box, confirm that the outer shell is not damaged, and check whether the items in the packaging box match those in the list;

·The upper part of the electric energy meter has hook screw holes, which are fixed with M4 hook screws. The lower part of the electric energy meter has two installation holes, which are fixed on the wall or terminal block with M4X10 or M4X12 self tapping screws (see the external dimension drawing);