Technical performance
|
Range of measurement |
0-10, 35... 1000KPa |
|
0~2…7MPa |
|
|
Overload pressure |
≤150% FS |
|
Forms of pressure |
differential pressure |
|
Measurement medium |
Gas and liquid compatible with 316L stainless steel |
|
Output signal |
Two relay outputsAlong the way4-20mA standard signal output (optional) |
|
Relay load |
30V/5A DC 240V/3A AC |
|
Range of upper and lower limit settings |
Relays can be set arbitrarily within the full range |
|
Supply voltage |
24VDC/220VAC |
|
accuracy |
±0.3%F.S ±0.5%F.S |
|
Long term stability |
≤± 0.3% F.S/year |
|
Medium temperature |
-20~+85℃ |
|
Response time |
≤1ms |
|
Load resistance |
R=(U-12.5)/0.02-RDAmong them: U is the power supply voltage, RDFor the internal resistance of the cable |
|
life |
>1×108Pressure cycle (25 ℃) |
|
Membrane material |
316l stainless steel |
|
Shell material |
1Cr18Ni9Ti |
|
Pressure interface |
M20 × 1.5 or user-defined |
|
Electrical Connection |
connecting terminal |
|
Protection level |
IP65 |
Product Features
Using differential pressure sensors
High precision, low latency, fast response
Integration of measurement, display, and control
Two control point relay outputs220VAC 3A
4-20mA standard signal output (optional)
The switch signal is reliable and has control function
Strong anti-interference ability and good long-term stability
Exterior structure