English

Shanghai Taixi Electric Co., Ltd
Home>Products>TXCPSD dual speed control and protection switch
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
  • Address
    No. 2550, Waibiaosong Road, Jiading District, Shanghai
Contact Now
TXCPSD dual speed control and protection switch
Overview: TXCPS is used as a switch, combined with contactors, electrical interlocks, and other accessories to form a dual speed electric controller T
Product details

Product Introduction

Overview
Using TXCPS as a switch, combined with contactors, electrical interlocks, and other accessories, a dual speed electric controller TXCPSD is formed, which is suitable for the control and protection of dual speed motors.
There are three types of dual speed motor controller configurations:
Configuration 1: High speed is fire protection type (overload and overcurrent only alarm without tripping), low speed is basic type;
Configuration 2: High and low speed uniformity is the basic type;
Configuration 3: The high and low speed are evenly distributed as fire protection type (special orders should be specified).
The product features, main circuit parameters, and accessory modules are the same as the basic model.

The meanings of each part of the product model are as follows




Product dimensions






Circuit diagram of dual speed motor operation control
Secondary power supply power protection Power supply model Fire damper limit switch Low speed local and remote manual control and interlocking running signal Low speed alarm signal stop signal High and low speed stop control Adjust on-site and remote manual control and interlocking running signal High speed alarm signal stop signal High speed operation contactor
short circuit fault short circuit fault

Note:
①. This diagram is applicable to the operation control of various types of dual speed motors, using both local and remote manual control.
② The control protector (2KBO) used for high-speed smoke exhaust can be selected as a fire-fighting product, which has the function of only alarming and not tripping when overloaded or overcurrent occurs, and tripping when short circuited, meeting the requirement of continuing to work under overload. The secondary control schematic is universal.
③ External high and low speed start. The stop button group can be installed on the box surface or wall.
④ SQ is the limit switch for the fire damper, and its operating equipment stops running; When there is no limit switch for the fire damper, the circuit is short circuited.

serial number symbol name Model and Specifications quantity remark
1 FU fuse RT18-32X/4A 1 With fuse indication
2 CPS1.2 Control protector CPS-□□/□□/□□□ 2 Please refer to the selection diagram
3 HG1.2 Green signal light AD11-22/20~220V 2 Increase or decrease as needed
4 HR1.2 red signal light AD11-22/20~220V 2 Increase or decrease as needed
5 HB1.2 Blue signal light AD11-22/20~220V 2 Increase or decrease as needed
6 HY1.2 Yellow signal light AD11-22/20~220V 2 Increase or decrease as needed
7 HW White signal light AD11-22/20~220V 1 Increase or decrease as needed
8 SF1.2,SS1. High and low speed start Stop button LAY (1 normally open, 1 normally closed) 3 One red, one green, and one yellow
9 SF3.4,SS2. External high and low speed start Stop button group Engineering design decision 1
Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!