1、 Product Overview
XJXGN □ -12 (CVF) solid insulated ring main unit switchgear is a new generation of environmentally friendly solid insulated ring main unit independently developed by our company. It is mainly composed of three functional units, namely, V unit (circuit breaker unit), C unit (load switch) and F unit (combined electrical unit). Each unit can be used independently or expanded freely. Its structure is divided into intelligent control instrument room, operating mechanism and primary part. The instrument room can be equipped with microcomputer protection (controller). The mechanism is a special spring operating mechanism. The primary part uses APG automatic gel process to completely seal the disconnector and arc extinguishing chamber in epoxy resin, and has a special joint and bus side. The design switch of the arc extinguishing chamber uses specialized copper chromium contact materials, R-type longitudinal magnetic field contacts, and a complete one-time sealing process. The arc extinguishing chamber has significantly improved short-circuit current breaking ability, stability, electrical life, temperature rise, and insulation level compared to previous arc extinguishing chambers (copper aluminum contact material, cup-shaped longitudinal magnetic field contact structure, and incomplete one-time sealing process). The operating mechanism adopts a spring operated mechanism that is integrated with the switch, that is, the isolation switch and the main switch spring operated mechanism are integrated as a whole, which can easily achieve interlocking, and the mechanism has fewer parts, reducing unnecessary transmission links, high reliability, and can be equipped with electric operation according to user needs.

In addition to the simulated opening and closing position display integrated on the panel, the internal isolation knife's closing, opening, and grounding contact status can be intuitively observed through the visual observation window in front of the cabinet.
2、 Model and meaning

3、 Environmental conditions for use
● Altitude: ≤ 5000m;
● Environmental temperature: -45 ℃~+65 ℃; The daily average value is not greater than+45 ℃;
Relative air temperature: daily average not exceeding 95%, monthly average not exceeding 90%;
An environment that is not significantly contaminated by corrosive or flammable gases;
There is no risk of fire or explosion, and there is no frequent severe vibration in the environment.
Note: When the environmental conditions are different or there are other special requirements, the manufacturer can negotiate to provide products under special usage conditions.
4、 Product reference standards
GB311.1-1997 "Insulation Coordination for Substation and Transmission Equipment";
IEC62271-1-2007 "High voltage switchgear and control gear - Part 1: General specifications";
IEC62071-2003 "1-52kV AC Metal Enclosed Switchgear and Control Equipment";
GB3906-2006 "3.6~40.5kV AC Metal Enclosed Switchgear and Control Equipment";
GB3309-1989 "Mechanical Testing of High Voltage Switchgear at Room Temperature";
GB16926-2009 "High voltage AC vacuum load switch fuse combination";
GB/T11022-2011 "Common Technical Conditions for High Voltage Switchgear and Control Equipment Standards";
GB1984-2014 "High Voltage AC Circuit Breakers";
GB1985-2004 "High Voltage AC Isolating Switches and Grounding Switches";
GB3804-2004 "3.6kV~40.5kV High Voltage AC Load Switches";
DL/T403-2000 "Technical Conditions for Ordering 12-40.5kV Indoor High Voltage Vacuum Circuit Breakers";
DL/T404-2007 "3.6-40.5kV AC Metal Enclosed Switchgear and Control Equipment";
Q/GDW730-2012 "Technical Conditions for 12kV Solid Insulated Ring Main Unit";
1016006-0010-A0 General Technical Specification for 12kV Solid Insulated Ring Main Unit of State Grid Corporation of China.
5、 Technical parameters

Schematic diagram of functional unit dimensions (mm)

A typical plan

Note: ● represents standard configuration ○ represents optional configuration

Typical combination scheme

Schematic diagram of functional unit dimensions (mm)

6、 Ordering Notice
The parameters in this plan are the standard configuration provided by our company. If the customer has no specific requirements, the company will supply according to the standard configuration. If it exceeds the requirements of this plan, please explain separately.