Overview
Name |
ID |
Product Description |
Δpmax |
Δps |
kvsRated flow coefficient when the valve is fully open |
nominal diameter |
|---|---|---|---|---|---|---|
MXF461.15-0.6 |
100325535 |
Continuous regulating three-way mixed flow/two-way electromagnetic regulating valve, flange connection, PN16, DN15, kvs 0.6, AC 24 V |
300 kPa |
300 kPa |
0.6 m3/h |
15 |
MXF461.15-1.5 |
100325536 |
Continuous regulating three-way mixed flow/two-way electromagnetic regulating valve, flange connection, PN16, DN15, kvs 1.5, AC 24 V |
300 kPa |
300 kPa |
1.5 m3/h |
15 |
MXF461.15-3.0 |
100325537 |
Continuous regulating three-way mixed flow/two-way electromagnetic regulating valve, flange connection, PN16, DN15, kvs 3, AC 24 V |
300 kPa |
300 kPa |
3 m3/h |
15 |
MXF461.20-5.0 |
100325538 |
Continuous regulating three-way mixed flow/two-way electromagnetic regulating valve, flange connection, PN16, DN20, kvs 5, AC 24 V |
300 kPa |
300 kPa |
5 m3/h |
20 |
MXF461.25-8.0 |
100325539 |
Continuous regulating three-way mixed flow/two-way electromagnetic regulating valve, flange connection, PN16, DN25, kvs 8, AC 24 V |
300 kPa |
300 kPa |
8 m3/h |
25 |
MXF461.32-12 |
100325540 |
Continuous regulating three-way mixed flow/two-way electromagnetic regulating valve, flange connection, PN16, DN32, kvs 12, AC 24 V |
300 kPa |
300 kPa |
12 m3/h |
32 |
MXF461.40-20 |
100325541 |
Continuous regulating three-way mixed flow/two-way electromagnetic regulating valve, flange connection, PN16, DN40, kvs 20, AC 24 V |
300 kPa |
300 kPa |
20 m3/h |
40 |
MXF461.50-30 |
100325542 |
Continuous regulating three-way mixed flow/two-way electromagnetic regulating valve, flange connection, PN16, DN50, kvs 30, AC 24 V |
300 kPa |
300 kPa |
30 m3/h |
50 |
MXF461.65-50 |
100325543 |
Continuous regulating three-way mixed flow/two-way electromagnetic regulating valve, flange connection, PN16, DN65, kvs 50, AC 24 V |
300 kPa |
300 kPa |
50 m3/h |
65 |

function
BPZ:MXF461..
Analog control valve with electromagnetic actuator for chilled water or hot water control, flange connection
A hybrid three-way or two-way valve with electromagnetic actuator, suitable for analog control of chilled water or low-temperature hot water in closed-loop systems. Equipped with positioning control, valve position feedback signal, spring reset, and manual function.

technical specifications
rated pressure |
PN 16 |
Working Voltage |
AC 24 V |
Positioning signal |
DC 0...10 V; DC 2...10 V; DC 4...20 mA |
positioning time |
<2 s |
Equipped with spring reset function |
A ->AB closed |
position feedback |
DC 0...10 V |
Protection level |
IP54 |
ambient temperature |
-5...45 °C |
Installation location |
Vertical to horizontal |
Allow work pressure |
1000 kPa |
leakage rate |
A -> AB: 0...0.02 % kvs |
Bypass leakage rate |
< 0.2 % of kvsvalue |
medium temperature |
1…130 °C |
Valve flow characteristics |
Equal percentage; linear |
Travel accuracy Δ H/H100 |
1:1000 |
valve body |
Cast iron EN-GJL-250 |
Valve internal material |
Chromium nickel steel/brass |
Technical Specifications Table |
N4455 |