1、 Overview of single-stage fire water pump products:
The XBD-W single-stage water pump fire pump is divided into two types: single suction single-stage and single suction multi-stage segmented. It is used to transport clean water without solid particles and liquids with physical and chemical properties similar to water. Single stage water pumps are mainly used for boosting water supply in fire protection systems, and can also be applied to water supply and drainage in factories and mines. The flow range of liquid transported by a single-stage water pump is 5-80L/s, the pressure range of a single-stage water pump is 0.2-2.25MPa, the matching power range of a single-stage water pump is 1.5-200kW, and the diameter range of a single-stage water pump is from φ 50 to φ 250mm.
2、 Main purpose:
The XBD-W single-stage water pump fire pump is mainly used for pressurized water supply in fire protection system pipelines. Single stage water pumps can also be applied to industrial and urban water supply and drainage, high-rise building pressurized water supply, long-distance water supply, heating, bathroom, boiler cold and warm water circulation pressurized air conditioning refrigeration system water supply and equipment matching, and other occasions.
If you have any questions about the above products, you can call 021-57239999 or click to consult experts for selection and quotation
user feedback
4、 Installation instructions
During installation, the weight of the pipeline should not be borne on the pump body, otherwise it may damage the water pump.
2. The pump and motor are integrated structures that have been calibrated by the manufacturer before leaving the factory, and do not require adjustment during installation, making installation very convenient.
3. The installation must tighten the anchor bolts, and the pump should be inspected at regular intervals to prevent loosening and avoid vibration during pump start-up, which may affect the performance of the pump.
4. In order to maintain convenience and ensure safety, a regulating valve should be installed on the outlet pipeline of the pump and a pressure gauge should be installed near the pump outlet. For high lift pumps, to prevent water hammer, a check valve should also be installed before the pump outlet gate valve to cope with sudden power outages and other power loss accidents, ensuring that the pump operates under optimal conditions.
5. When the pump is used in situations with suction, it should be equipped with a bottom valve, and the inlet pipeline should not have too many bends. At the same time, there should be no air or water leakage to avoid affecting the suction capacity of the pump.
To prevent impurities from entering the pump and blocking the flow path, a filter should be installed before the pump inlet to improve performance.
7. The pump should be tested regularly (usually 15-20 days) for about 1 hour to prevent the shaft from getting stuck and unable to operate in emergency situations.
For installation related questions, you can call 021-57239999 or click to consult experts for selection and quotation
5、 Instructions for use:
Before startup:
1. The hood should be opened and manually turned to check for flexibility.
2. Open the inlet valve and exhaust valve to fill the pump chamber with water, and then close the exhaust valve.
3. Tap the motor to confirm if the steering is correct.
function:
1. Fully open the inlet valve and close the outlet pipeline valve.
2. Connect the power supply, and when the pump speed reaches normal, open the outlet pipeline valve and adjust it to the desired operating point.
3. Observe whether there are any abnormal situations after the pump is running. If there are any abnormal situations, stop the pump immediately for inspection, handle them before running again.
parking:
1. After gradually closing the outlet valve, cut off the power supply.
2. Close the inlet valve.
3. If the ambient temperature is below 0 ℃, measures should be taken to keep warm.