Harmonic complex rate power meter
Harmonic complex rate power meter
Product details

◆ Overview

The AT2008 three-phase complex rate harmonic multifunctional power meter adopts digital signal processing chips and high-precision energy metering chips, which can accurately and stably measure all commonly used power parameters in the three-phase power grid, including three-phase voltage, three-phase current, active power, reactive power, apparent power, grid frequency, power factor, four quadrant energy, voltage imbalance, current imbalance, voltage total harmonic and sub harmonic content, current harmonic total harmonic and sub harmonic content, zero sequence current, UIPQ demand, time-sharing billing with four rates and eight time periods, switch input monitoring, relay output control, and equipped with two RS485 communication interfaces, active energy pulse output and reactive energy pulse output. Functions such as pulse output, SOE event recording and alarm.

As an advanced intelligent and digital front-end acquisition unit for power grids, three-phase complex rate harmonic multifunctional power meters have been widely used in various control systems, SCADA systems, energy management systems, substation automation, distribution network automation, residential power monitoring, industrial automation, intelligent buildings, intelligent distribution panels, and switchgear. They have the advantages of easy installation, simple wiring, easy maintenance, small engineering quantity, programmable input parameters on site, and the ability to complete group network communication with different PLCs, frequency converters, industrial control computers, etc. in the industry. All products are self-developed and produced by our company, supporting customized functions. Please contact our company for details.

◆ Function Introduction


Measurement function

prepare note

real-time measurement

three-phase voltage

Basic functions

three-phase current

Power, frequency, power factor

electricity metering

active energy

Reactive energy

Bidirectional measurement

demand

UIPQslip

Extended features

Harmonic measurement

Total harmonic content2-31Sub harmonic and subharmonic content31time

multi-rate

4Seed rate8atime slot

Electric energy pulse

Active and reactive passive node outputs

transmitter output

4-20mA/0-5V

Switch input

Passive node

relay output

AC250V/5Aremote control/call the police

Event log

call the police

communication

RS485interfaceMODBUS-RTU

1Road or2Road)

display mode

LCDLCD (Liquid Crystal Display)


◆ Technical parameters

performance

ginseng number

lose

enter

measure

quantity

apparent

show

network

Three phase three wire, three phase four wire

voltage

rated value

AC380V/100V

overload

continued:1.2times Instantaneous:10times/10s

merit consume

<1VA(Each phase)

block resist

>500kΩ

essence degree

RMSMeasurement, accuracy level0.5level

current

rated value

AC0-5A

overload

continued:1.2times Instantaneous:10times/10s

merit consume

<0.4VA(Each phase)

block resist

<2mΩ

accuracy

RMSMeasurement, accuracy level0.5level

frequency rate

45-65Hz

merit rate

Visual power, active power accuracy0.5Grade, reactive power accuracy1.0level

electricity can

Four quadrant measurement, active poweraccuratedegree1.0Grade, reactive poweraccuratedegree1.5level

harmony wave

Total harmonic content2-31Sub harmonic and subharmonic content2-31time

power supply

scope of work

AC220VorAC/DC80-270V

merit consume

3VA

output

digital interface

RS-485interfaceMODBUS-RTUAgreement orDLT645-1997/2007

pulse output

2Pulse output of road electrical energy,Pulse constant:5000imp/kWh

environment

working environment

-10-55

storage environment

-20-75

safety

endure press

>2.5kV/1min

cease fate

Input, output, and power supply to the chassis>500MΩ

Electric energy measurement range

Measurement range of active and reactive electricity0-kWh,

Exceeding this value, the electrical degree will be0Start counting



◆ External dimensions


Panel Size

L×H mm

installation dimensions

(A×B mm)

cutout size

(S×Y mm)

Chief of Staff

N mm

depth

M mm

96×96

91×91

92×92

93

78


Typical wiring diagram

1. Backboard terminal diagram

2. Functional Description of Wiring Terminals


power supply

1,2

AC220VorAC/DC80-270V

current signal

4,5,6,7,8,9

468forA,B,CPhase current inlet

voltage signal

11,12,13,14

Three phase voltage input respectivelyUATheUBTheUCTheUN

relay output

15,16,17,18,19,20,21,22

4Road relay output

transmitter output

30-34

4Road transmission output,30For the public end

Electric energy pulse

47,48,49,50

47,49For passive output positive terminal

485interface

5859

respectivelyA+TheB-

Discrete input

70-78

8Road switch input,70For the public end