- Product Introduction
MC-FC dust particle transmitter
Product User Manual

Beijing Mengchuang Weiye Technology Co., Ltd
Our company solemnly promises that for users who purchase our sensors, we will provide free one-on-one serviceTechnical support (knowledge of wiring methods, data analysis, maintenance, etc.) until the user masters the use.
|
1 |
product overview |
MC-FCType dustThe transmitter adopts imported laser module and photosensitive element. Fine calibration has been carried out during production, and the calibration data is stored in the internal memory. Sensors have the characteristics of digital output and complete interconversion, without the need for complex verification and calibration processes. They excel in measurement accuracy, linearity, repeatability, interconversion, consistency, and other aspects. They are designed with temperature compensation circuits and can be used at different environmental temperatures.
|
2 |
Product Features |
1AdoptingConstant wind pressure and pedestrian flow adaptation technology make measurement more accurate and reliable.
2、Using deep algorithms to optimize compensation.
3、Structural design of anti dust sensor.
4Full range temperature and humidity compensation, wide measurement range, optional measurement range
5Flexible installation, easy to use, small size, light weight, anti vibration
6Can be made into various shapes to meet the needs of different customers
|
3 |
scope of application |
Widely used in fields such as meteorological stations, greenhouses, environmental monitoring stations, medicine and health, purification workshops, precision laboratories, etc. that require monitoring of the overall environment.
|
4 |
Product Information |
Gas detection:PM1.0、PM2.5、PM10
Range:0-1000ug/M3
Minimum resolution particle diameter:0.3 micron
response time≤ 10 seconds
Output data:UART output (3V level)
DAC (0-2V corresponds to 0-1000)
PWM output
Working voltage:5V±0.1V
Working current:70-140(mA)
Sleep current:<10mA
Response time:≤ 90 seconds
Working humidity:15% RH-80% RH (non condensing)
Working temperature: -20~40℃
Storage temperature: -40~60℃
service life:3 years (in the air)
|
5 |
Usage |
Attention: Be careful when wiring. If the power supply voltage is too high or the polarity is reversed, it will cause permanent damage to the sensor
|
6 |
Product appearance |



|
7 |
Data Conversion Methods |
dustRS485message
Modify Address
10Function code write address instruction:00 10 80 00 00 01 02 00(New address) (Low checksum) (High checksum)



|
8 |
Precautions for use |
1When receiving the product, please check if the packaging is intact and verify if the transmitter model and specifications match the product you have purchased;
2The installation site should be kept away from chemical corrosive environments;
3The transmitter and wires should be kept away from high voltage electricity, heat sources, etc;
4The transmitter is a precision instrument and should be stored in a dry, ventilated, and room temperature indoor environment;
5Sensors are precision components. Users are advised not to disassemble them themselves during use to avoid product damage
|
9 |
Product Warranty |
The warranty period for this product is one year. Within twelve months from the date of shipment, if the malfunction is caused by sensor quality issues (non-human damage), our company is responsible for free repair or replacement. After the warranty period, only the cost fee will be charged.
Address: Building 3, Courtyard 2, Longxiang Plate Making Group, Huilongguan Town, Changping District, Beijing206
contacts: Song Xuewen (Same WeChat account)
Telephone:
Fax: enterpriseQQ:949219322
website:www.sul2100.cnE-mail:bj6213@126.com