Shanghai Renming Electric Meter Co., Ltd
Home>Products>DTSD2255 Three phase Four wire Electronic Multi functional Energy Meter
Product Groups
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
    13585777355
  • Address
    Building F237, No. 2, Lane 158, Luoye Road, Xiaokunshan Town, Songjiang District, Shanghai
Contact Now
DTSD2255 Three phase Four wire Electronic Multi functional Energy Meter
Brief introduction
Product details


1、 Product Introduction


The DTSD2255 energy meter is a multifunctional energy meter independently developed and produced by our company. This product adopts ultra-low power large-scale integrated circuit technology and SMT manufacturing process, and has the characteristics of high measurement accuracy, stable performance, high quality, and excellent EMC performance. It has the function of measuring positive and negative active energy, four quadrant reactive energy, recording time-sharing energy at four different rates, and recording various events during the operation of the meter (such as voltage, current, power factor, load, demand, and programming events). It has infrared communication and dual RS485 communication functions. Equipped with power-off meter reading batteries, it can achieve infrared meter reading function during power outages. The performance indicators of this meter comply with the technical requirements of GB/T17215.321-2008 "Level 1 and Level 2 Static AC Active Energy Meters", GB/T 17215.301-2007 "Special Requirements for Multifunctional Energy Meters", and DL/T614-2007 "Multifunctional Energy Meters" standards for multifunctional energy meters. Its communication meets the requirements of DL/T645-2007 "Multifunctional Energy Meter Communication Protocol".

1.1 Working principle

This three-phase multifunctional electric energy meter is composed of a measuring unit and a data processing unit. In addition to measuring active (reactive) electric energy, it also has two or more functions such as time-sharing and measuring demand, and can display, store, and output data. The working principle diagram is shown in Figure 1:

Working principle diagram

It consists of a measuring unit and a data processing unit (CPU), LCD, infrared communication port, dual RS485 communication, RS232 communication port, etc. When the electric energy meter is working, the analog signals (voltage, current) are processed by the measuring chip into digital signals, and the CPU performs arithmetic processing to store the data. The reading and parameter setting of electricity data and other information can be done through a handheld computer or a dedicated software combined with an upper computer. An infrared remote control can also be used to query any display item of the electricity meter in conjunction with a display meter.


1.2 Technical indicators
a. Reference standards: DL/T614-2007 "Multifunctional Energy Meter", DL/T645-2007 "Multifunctional Energy Meter Communication Protocol"
b. Accuracy level: Active power level 0.5, reactive power level 2.0
c. Working voltage: 220/380V
d. Working current: mutual inductance type 1.5 (6) A
e. Starting current: active 0.002In (1.0)
0.003In (2.0)
f. Stealth: with anti creep logic design
g. Pulse constant: 200-12800 imp/kWh
h. Rated frequency: 50Hz ± 5%
i. Meter lifespan:>15 years
j. Dimensions: 293mm  175mm  80mm
k. Weight approximately: 2.9kg

l. Electrical parameters
Normal operating voltage: 0.8Un~1.2Un
Maximum operating voltage: 0.75Un~1.25Un
Voltage line power consumption: ≤ 1.5W and 4VA
Current line power consumption:< 1VA
Data backup battery voltage: 3.6VDC
Power outage meter reading battery voltage: 6 VDC

m. Rate work parameters
Clock accuracy (daily error): ≤ 0.5 s
Battery capacity: ≥ 1200 mAh
Data retention time after power outage: ≥ 10 years (using new batteries)

n. Climate conditions
Normal operating temperature:- 20℃~+75℃
Storage and transportation temperature:- 25℃~+85℃
Storage and working humidity: ≤ 95%

o. Technical parameters
Number of rates: 4
Number of time periods: 10 × 4
Calculation range: 0-99999.99 kWh, 0~999999.99 kvarh
Display: LCD
Communication baud rate: RS485 ① port 300-9600 bps, RS485 ② port 1200bps Infrared communication port: 1200bps, RS232 (optional)
Communication protocol: DL/T645-2007 Multifunctional Energy Meter Communication Protocol, Zhejiang Province Single and Three Phase Electronic (Time Division) Energy Meter Communication Protocol (Trial) (V3.0)

1.3 Product specifications: See the table below (can be customized according to specific user needs):

Operating Voltage

0.8Un1.2Un

Extreme working voltage

0.75Un1.25Un

Voltage line power consumption

1.5Wand4VA

Power consumption of current circuit

1VA

Data backup battery voltage

3.6VDC

power failureMeter reading battery voltage

6 VDC



2、 Outline drawing