CHCS-LFH-1005Series closed-loop high-precision Hall current sensor(Instruction manual download:)
CHCS-LFH-1005The series sensor is based on the principle of closed-loop magnetic balanceMulti Hall, double-layer structure with high precisionHall current sensor,A true resolution of 1:1000. And it overcomes the errors caused by geomagnetic or line diameter thickness and position differences, with high accuracyMeasure DC, AC, pulse, and various irregular currents.
yield product special sexually |
answer use |
·high-precision
·Good linearity
·Low temperature float
·Short response time
·High anti-interference ability
·Strong current overload capability |
·Static DC motor drive
·Variable speed drive application
·Current monitoring and battery application
·switch power supply
·UPS uninterruptible power supply
·Inverter power supply and Application of Welding Power Source |
Electrical characteristics:
|
CHCS-LFH-1005 |
|||
Rated current IPN(A) |
10A-1000A |
|||
Measurement Range IP(A) |
±2000A |
|||
Measure resistance RM(Ω) |
With±15V |
@±1000Amax |
0 Ω(min) |
20Ω(max) |
@±1200Amax |
0Ω(min) |
7.5Ω(max) |
||
With±24V |
@±1000Amax |
0Ω(min) |
65Ω(max) |
|
@±2000Amax |
0Ω(min) |
7.5Ω(max) |
||
Wire turn ratio |
1:5000 |
|||
Internal resistance of secondary coil |
@ 70℃50Ω |
|||
Rated output current ISN(mA) |
2±0.1%FS(10A), 200±0.1%FS(1000A) |
|||
Power supply voltage Vc(±5%) |
±15V-±24V |
|||
Isolation voltage |
50Hz, 1min,6.5kV |
|||
Current loss Ic (mA) |
≤20+Ip/Ns |
Dynamic characteristics:
Accuracy XG @IPN,T=25°C |
±0.2 |
% |
Zero offset current Io@IP=0,T=25°C |
≤±0.2 |
mA |
Imbalance current temperature drift@ -45°C--85°C |
≤±0.5 |
mA |
Linearityεr |
<0.1 |
%FS |
di/dtFollow accuracy |
>100 |
A/µs |
Response time tr |
<1 |
µs |
bandwidth(-3db) |
DC~150 |
kHz |
General characteristics:
working temperature |
-40 ~+85 |
°C |
Storage temperature |
-40~+125 |
°C |
Working humidity |
20-90 no condensation |
% |
Actual weight |
570 |
g |
Other:
authentication |
CE |
quality system |
ISO9000 |
ISO14001 |
|
Execution standards |
SJ20790-2000; JB/T 7490-2007 |
Lead free process, shell and components comply with UL94-V0 |
Structural diagram (mm)
Main tolerances:
·Total tolerance ± 0.5mm
·Install vertical positions with 4 holes of diameter 4.2mm and 2 holes of diameter 5.3mm
·Horizontal position with 4 holes and a diameter of 5.3mm
·Primary aperture 40.5mm * 38.5mm
·Connector MOLEX 5045-03A
usage method:
1.When IP flows in the direction of the arrow, IS is forward;
2.The temperature of the primary conductor should not exceed 100 ℃;
3. The optimal dynamic performance (di/dt and response time) is achieved when the mother row is fully filled with primary perforation;
4.To achieve optimal magnetic coupling, the primary wire turns should be wound around the top of the sensor;
5. Products can be customized according to customer requirements.