ASCO Asca solenoid valve 8210G014 detailed technical data positioning This valve is used to perform correct installation in any position at any time.
Product details

ASCO Asca Electromagnetic Valve 8210G014 Detailed Technical Data

The positioning of this valve is used to perform correct installation in any position at any time. However, the most optimal life and performance, solenoid valve
It should be installed vertically to reduce the possibility of foreign material accumulation in the solenoid coil assembly area.
Connect the pipeline to the valve according to the markings on the valve body. Male compound or polytetrafluoroethylene tape coated tube thread
Only. If applied to valve threads, compounds may enter the valve and cause the operation to fail to delegate authority. Avoid normal pipeline pressure
Support and adjust pipelines. When tightening the pipeline, do not use valves or solenoid valve stems. The positioning wrench is suitable for connecting the valve body or pipeline as much as possible.

All solenoid valves should be cleaned regularly. The cleaning time between them will depend on the medium and service conditions. Generally speaking, if the voltage of the coil is correct, slow valve operation, excessive noise or leakage will indicate that cleaning is necessary. In extreme cases, incorrect valve operation may occur and the valve may fail
Open or close. Clean the filter or filter when cleaning the valve. Preventive maintenance keeps the medium fl free from dirt and foreign materials through valves.
Valves that undergo regular exercise should take into account environmental or fluid conditions such as corrosion, elastomer degradation, fluid contamination, which may hinder or affect other conditions
It is possible to change the solenoid valve. The actual frequency of exercise will depend on specific operating conditions.
A successful operation history is a periodic motion with appropriate prompts. Periodic based on the medium and service conditions
Suggestions for inspecting damaged or excessively worn internal parts of the valve. Thoroughly clean all components. If worn or partially damaged, install a complete reconstruction kit.
ASCO Asca Electromagnetic Valve 8210G014 Detailed Technical Data

Electromagnetic valve: used for switch control of liquid and gas pipelines, it is a two position DO control. Generally used for controlling small pipelines.
Electric valve: Used for analog regulation of medium flow in liquid, gas, and air system pipelines, and is AI controlled. Electric valves can also be used for two position switch control in the control of large valves and air systems.
Electromagnetic valve: can only be used as a switch quantity, is DO control, can only be used for small pipeline control, commonly seen in pipelines of DN50 and below.
Electric valve: It can have AI feedback signals and can be controlled by DO or AO, which is more commonly seen in large pipelines and air valves.
1. Switch form:
The solenoid valve is driven by a coil and can only be turned on or off, with a short action time when turned on or off.
The driving of electric valves is usually done by motors, and the opening or closing action requires a certain amount of time for analog measurement, which can be adjusted.
2. Job nature:
Electromagnetic valves generally have a small flow coefficient and a small working pressure difference. For example, the flow coefficient of a typical 25 caliber solenoid valve is much smaller than that of a 15 caliber electric ball valve. The drive of solenoid valves is through electromagnetic coils, which are relatively easy to be damaged by voltage surges. Equivalent to the function of a switch, it has two functions: on and off.

1. Disassemble the valve and use an exploded view to identify the cation and position parts in an orderly manner. Or 1 ¼ "NPT valve structure or optional manual
Operator. Construction of nuclear treaty valves.
2. Eliminate electromagnetic field. See separate instructions. Use a specialized wrench to loosen the electromagnetic foundation assembly
Provided in the adapter reconstruction toolkit. For special wrench adapters, there is no ASCO wrench kit for the order. K218950。 Eliminate electromagnetic foundation sub assembly, core, plug-in assembly, and electromagnetic foundation pads. Unscrew the adapter from the valve body and remove the valve disc retainer
Assembly, valve disc retainer spring, and valve cover gasket. Normal maintenance (cleaning) is not necessary
Eliminate the valve seat. However, a 7/16 "thin-walled socket wrench is used for the valve seat.
ASCO Asca Electromagnetic Valve 8210G014 Detailed Technical Data